Wolf WK-101 System klimatyzacji i wentylacji
Specyfikacje
Overview
Supply Air Unit Wolf WK-101
- Nominal volume flow
- 8500 m³/h or 2.36 m³/s
- Total delivery pressure
- 675 Pa
- Exact delivery pressure
- 250 Pa
- Fan efficiency
- 75.3%
- Fan speed
- 2131 rpm
- Fan power
- 2.4 kW
- Differential pressure
- 1861 Pa
- Motor power
- 3 kW
- Motor speed
- 1420 rpm
Extract Air Unit Wolf WK-101
- Nominal volume flow
- 8500 m³/h or 2.36 m³/s
- Number of filters
- 4
- Filter class
- F5
- Filter type
- Biost Pocket filter TK F5 PVC
- Initial pressure difference
- 69 Pa
- Final pressure difference
- 200 Pa
Heater Wolf WK-101
- Nominal volume flow
- 8500 m³/h or 2.36 m³/s
- Nominal heat output
- 51.4 kW
- Air inlet temperature
- -14°C
- Air outlet temperature
- 4°C
- Heating medium
- Water-glycol
- Flow temperature
- 12.8°C
- Return temperature
- 0.7°C
- Medium flow rate
- 4240 l/h
- Glycol content
- 30%
- Max. operating temperature
- 120°C
- Pressure difference air
- 0 Pa
- Pressure difference water
- 29.5 Pa
Czy jesteś zainteresowany tą maszyną?
Skontaktuj się ze sprzedawcą, aby dowiedzieć się więcej, omówić cenę lub umówić się na oględziny.
Skontaktuj się ze sprzedawcą
Znasz kogoś, kto mógłby być zainteresowany?
Udostępnij tę maszynę współpracownikom lub znajomym
Udostępnij tę maszynę
Opis AI
BetaMożliwości
This complete Wolf WK-101 air conditioning and ventilation system includes a supply air unit, extract air unit, and heater—designed to handle high-volume air processing for industrial facilities. The supply unit delivers 8,500 m³/h with a 3kW motor, while the extract unit features four F5-class filters for effective air purification. Together, they maintain controlled temperature and air quality across large spaces like manufacturing plants, chemical facilities, warehouses, and cleanrooms.
Branże i zastosowania
Chemical plants, pharmaceutical companies, food processing facilities, and industrial manufacturers rely on systems like this to protect product quality, ensure worker safety, and meet environmental regulations. The dual-unit design allows simultaneous fresh air intake and contaminated air removal, essential for processes sensitive to dust, humidity, or airborne particles.
Na co zwrócić uwagę przy zakupie
When evaluating this 2008 system, request complete maintenance records and filter replacement history—frequent filter changes indicate proper upkeep. Inspect motors and fan blades for corrosion or imbalance, check seals for leaks, and verify electrical connections. Ask about operating hours and any repairs performed. Given the system's age, budget for potential motor servicing and filter stock. Confirm all three components (supply, extract, heater) operate together as a coordinated unit before purchase.
Ten opis został wygenerowany przez AI i ma charakter wyłącznie ogólnego przewodnika. Podobnie jak w przypadku wszystkich treści generowanych przez AI, mogą wystąpić nieścisłości. Przed podjęciem decyzji o zakupie zweryfikuj wszystkie szczegóły bezpośrednio ze sprzedawcą.
Czy jesteś zainteresowany tą maszyną?
Skontaktuj się ze sprzedawcą, aby dowiedzieć się więcej, omówić cenę lub umówić się na oględziny.
Skontaktuj się ze sprzedawcą
Podobne maszyny
Inne maszyny w kategorii Filter systems
Znasz kogoś, kto mógłby być zainteresowany?
Udostępnij tę maszynę współpracownikom, partnerom lub znajomym, którzy mogą szukać podobnego sprzętu.